Chapter 4 Explanation of Functions
4-75
4.2.83 Initialization setting
The initialization function allows you to initialize the adjusted settings on the
inverter to restore the factory settings. You can also clear the trip history data
alone.
The settings of initialization are described below. Running-time data and power-on time data cannot be cleared.
Initialization mode
(parameters or trip
history)
Clearing on the trip history data
Initializing only the settings
The factory settings are restored.
Clearing the trip history data and initializing the
settings
Clearing the trip history data and initializing the
settings and EzSQ program
Country code for
initialization
Defaults intended for Japan
Defaults intended for Europe
Defaults intended for the U.S.A.
(Initializing procedure)
Adjust the above settings as required, and then perform the following procedure:
Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121, C122, and
C123) and thermistor coefficient setting (C085).
Note 2: The initialization operation does not initialize the settings of easy sequence user parameters (P100 to P131).
b084: Initialization mode (parameters or
trip history)
b085: Country code for initialization
1) Set b180=01 and press the STR.
Or
Holding down the FUNC and [2]
(down) keys, press and hold down the
STOP/RESET key.
- After the monitor starts blinking,
release only the STOP/RESET key.
(The display on the monitor changes
to that shown in the middle figure
above.
- Release the FUNC and [2] (down)
keys.
2) Initialization is in progress.
- The above figure shows the monitor
display (indicating that the
initialization is in progress) intended
for Japan. Those intended for other
regions and trip history clearance are
shown below.
3) When the initialization is completed,
the monitor displays data "0.00".
(In case of b038 = 001)
Confirm that the settings have been
initialized.
Initialization-in-progress display
intended for Europe
Initialization-in-progress display
intended for the U.S.A.
Initialization-in-progress display for
trip history clearance
In the far-left digit, the lighting
segments move round for about
2 seconds.