Chapter 4 Explanation of Functions
4-126
(xii) 0B command: This command recalculates the constants set in the inverter.
This command must be issued when the base frequency or the setting of parameter "H***" has been changed for the
RS485 communication.
- Transmission frame
Frame format
Control code (Start of TeXt)
Station number of control-target
inverter
Command to be transmitted
XOR of the items from "Station No." to "Data." See
Item (3) of this section.
Control code (Carriage Return)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.