(3) How to calculate the block check code (BCC)
(Example) When using the 01 command (frequency-setting command) to set the inverter output frequency to 5 Hz
(the station No. of the inverter is 01):
The contents of "Station No." to "Data" are converted into ASCII data, and the ASCII data is XORed bit by bit. The final
XOR result is set as the block check code (BCC). In the above example of transmission frame, BCC is calculated as
follows:
(Reference) ASCII code conversion table
05 (This result is used as BCC.)
Transmission frame configuration