Chapter 2 Installation and Wiring
2-18
(4) Recommended cable gauges, wiring accessories, and crimp terminals
Note: For compliance with CE and UL standards, see the safety precautions concerning EMC and the compliance
with UL and cUL standards under Safety Instructions.
The table below lists the specifications of cables, crimp terminals, and terminal screw tightening torques for
reference.
Note: Cable gauges indicate those of HIV cables (maximum heat resistance: 75°C).
Note: *** is described as FF, FEF or FUF.
Note: Please use the round type crimp terminals (for the UL standard) suitable for the use electric wire when you connect the
electric wire with the main circuit terminal stand. Please put on pressure to the crimp terminals l with a crimp tool that the
terminal stand maker recommends.
Applicable inverter
model
Gauge of
power line
cable (mm
2
)
(Terminals: R,
S, T, U, V, W,
P, PD, and N)
External braking
resistor across
terminals P and
RB (mm
2
)
Earth-leakage
breaker (ELB)
SJ700D-1320HFF3
SJ700D-1320HFEF3