3-15
Example 3: Frequency command source Setting data in F001 (Control panel) + multi speed select
Run command source External signal (Control terminal)
(1) I/O connections
*) In case of SJ700D-****FUF3, you need to set C006=03 and C016=00.
*) You need to set multi speed frequency command into parameters (from A020 to A022).
*) Refer to 3.5.2 for changing the frequency command source and 3.5.3 for changing the run
command source.
(2) Operation
Frequency: By using the multi speed terminals, set the frequency command.
Run/Stop: Using the forward / reverse terminal to run and stop.
(3) Parameter settings
Control circuit terminal block
Multi speed 1 and 2 are not active.
Multi speed 1is active and
multi speed 2 is not active.
Multi speed 1is not active and
multi speed 2 is active.
Note) Initial settings are 0.00Hz. You need to set the appropriate data.