Description of the I/O Modules Excel 800
EN1B-0375GE51 R0910
54
Manual Override in the AUTO Position
When a manual override of the …R824 Relay Output
Module is set to the “AUTO” position, and the corresponding
relay output has been configured, the following applies:
If the LONWORKS network is functioning properly, the
logical status of the relay output will be “AUTO.”
If the LONWORKS network is not functioning properly, the
feedback signal will be switched to the safety position
value.
The feedback signal on the LONWORKS network:
nvoDoActPosnFb[ ] will have a value of either 0% or
100%, and a state of -1.
The status LED (yellow) will indicate the actual logical
state of the relay output as commanded (by
nviDoSwitch[ ]).
When a manual override of the …
R824 Relay Output
Module is set to the “AUTO” position, and the corresponding
relay output has
not been configured, the following applies:
Regardless as to whether the LONWORKS network is
functioning properly or not, values from the L
ONWORKS
Bus will be ignored, and there will be no heartbeat or
safety position.
The feedback signal on the LONWORKS network:
nvoDoActPosnFb[ ] will have a value of 0% and a state
of 0.
The status LED will be unlit.
Manual Override in the ON Position
When a manual override of the …R824 Relay Output
Module is set to the “ON” position, the following applies:
If the relay output has been configured, its logical state
will depend upon the actual output configuration.
If the relay output is unconfigured, it will be switched ON.
Regardless of configuration, the feedback signal on the
L
ONWORKS network: nvoDoActPosnFb[ ] will have a
value of 1000…0% and a state of -1.
Regardless of configuration, the status LED (yellow) will
flash to indicate “manual override.”
Manual Override in the OFF Position
When a manual override of the …R824 Relay Output
Module is set to the “OFF” position, the following applies:
If the relay output has been configured, its logical state
will depend upon the actual output configuration.
If the relay output is unconfigured, it will be switched
OFF.
Regardless of configuration, the feedback signal on the
L
ONWORKS network: nvoDoActPosnFb[ ] will have a
value of 0% (direct) or 100% (reverse) and a state of -1.
Regardless of configuration, the status LED (yellow) will
flash to indicate “manual override.”
Note
Panel Bus I/O modules feature watchdog functionality. Con-
sequently, if the module’s firmware stops running (due, e.g.,
to updating), the watchdog will switch OFF the module’s
outputs – even if the corresponding manual overrides (if
present) have been set to ON. Thus, the manual overrides
should NOT be thought of as emergency overrides; rather,
they are subordinate to the given Panel Bus I/O module’s
processor and firmware.