EasyManua.ls Logo

Honeywell Fire-Lite Alarms MS-9050UD - Page 175

Honeywell Fire-Lite Alarms MS-9050UD
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Central Station Communications
MS-9050UD PN 52413:C 01/23/08 175
The table below shows UL listed receivers which are compatible with the MS-9050UD.
1. With version 3.9 software
2. With 685-8 Line Card with Rev. 4.4d software
3. With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software
4. With 124077V2.00 Receiver and 126047 Line Card Rev. M
5. With V.7301 Receiver S/W
6. With 01.01.03 Receiver S/W and Line Card 01.01.03
7. Surgard System III software version 1.6
8. Surgard MLR-2 software version 1.86
9. With DSP4016 and V1.6 Line Card
10. With 124060V206B and 124063 Line Card Rev. B
IMPORTANT! It is the installers responsibility to ensure that the Digital Alarm Communicator/
Transmitter is compatible with the Central Station Receiver, utilized by the monitoring service,
prior to installation. The Compatibility Table provides a list of compatible receivers and
associated software versions for the receivers. Changes in the hardware and/or software by the
receiver manufacturers may affect the receiver compatibility with the FACP DACT. After
completing the installation, communication between the DACT and Central Station Receiver must
be tested and verified.
Table 5.3 Compatible UL Listed Receivers
Format
FBI
CP220FB (1)
Ademco
685 (2)
Silent Knight
9000 (3)
Silent Knight
9800 (4)
Osborne Hoffman
2000E (5)
Radionics
6600 (6)
Surgard
System III(7)
Surgard
MLR-2(8)
Surgard
MR-2000(9)
Ademco
MX8000(10)
4+1 Ademco Express

4+2 Ademco Express

3+1/Standard/1800/2300

3+1/Expanded/1800/2300

3+1/Standard/1900/1400

3+1/Expanded/1900/1400

4+1/Standard/1800/2300

4+1/Expanded/1800/2300

4+1/Standard/1900/1400

4+1/Expanded/1900/1400

4+2/Standard/1800/2300

4+2/Expanded/1800/2300

4+2/Standard/1900/1400

4+2/Expanded/1900/1400

Ademco Contact ID

Not Used

Table of Contents