Programming
MS-9050UD PN 52413:C 01/23/08 51
SECTION 3 Programming
3.1 Programming Data Entry
Programming can be accomplished using the MS-9050UD keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J6 on the
control panel main circuit board.
The information presented in this section refers to programming the MS-9050UD via the onboard
keypad. If an optional computer keyboard is connected to the MS-9050UD main circuit board, the
following table describes the keyboard keys which correspond to the onboard keypad keys.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan-
dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be lim-
ited to specific values or not used at all as indicated below:
Program feature
or option
Permitted in
UL 864? (Y/N)
Possible settings
Settings permitted in
UL 864
Trouble Call Limit N
Refer to "Trouble Call Limit (Dialer Runaway Preven-
tion)" on page 121.
Trouble Call Limit = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Trouble Call Limit = 0
for unlimited Central
Station
trouble calls
Remote Download Y
Refer to "Remote Download" on page 176.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Remote Download
Proprietary Yes for
Proprietary
Installations Only
Keypad Keys Computer Keyboard Keys
1st Event Home
CLR Delete
ESC Esc
RECALL Insert
**
##
A - Z A - Z
0 - 9 0 - 9
(on QZ key)
Space bar
——
//
••




ENTER Enter
ACK/STEP F1
SILENCE F2
DRILL F3
RESET F4