Power Supply Calculations
MS-9050UD PN 52413:C 01/23/08 181
Table 7.3 contains columns for calculating current draws. For each column, calculate the current
and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 7.4 on page 182.
Table 7.3 System Current Draw Calculations
Device Type
Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)
Calculation Column 2
Primary, Fire Alarm Current
(amps)
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Qty X[current draw]= Total Qty X [current draw] = Total Qty X[current draw]= Total
Main Circuit Board 1 X[0.120]= 0.120 1 X[0.200]= 0.200 1 X[0.120]= 0.120
4XTMF [ ] X[0.005]= [ ]
X[0.011]
1
=
[ ] X[0.005]=
4-wire Detector Heads [ ]
X[ ]
2
=
[ ] X[ ]= [ ] X[ ]=
Power Supervision
Relays
3
[ ] X[0.025]= [ ] X[0.025]= [ ] X[0.025]=
CP350 & CP355 [ ] X[0.00030]=
maximum alarm draw
for all devices
0.400
[ ] X[0.00030]=
SD350 & SD355 [ ] X[0.00030]= [ ] X[0.00030]=
SD350T & SD355T [ ] X[0.00030]= [ ] X[0.00030]=
AD350 & AD355 [ ] X[0.00030]= [ ] X[0.00030]=
H350 & H355 [ ] X[0.00030]= [ ] X[0.00030]=
H350R & H355R [ ] X[0.00030]= [ ] X[0.00030]=
H355HT [ ] X[0.00030]= [ ] X[0.00030]=
D350P [ ] X[0.00030]= [ ] X[0.00030]=
D350RP [ ] X[0.00030]= [ ] X[0.00030]=
B501BH & B501BHT
4
[ ] X[0.001]= [ ] X[0.001]=
B224RB Relay Base [ ] X[0.00050]= [ ] X[0.00050]=
B224BI Isolator Base [ ] X[0.00045]= [ ] X[0.00045]=
MMF-300 [ ] X[0.00040]= [ ] X[0.00040]=
MMF-300-10 [ ] X[0.00350]= [ ] X[0.00350]=
MDF-300 [ ] X[0.00075]= [ ] X[0.00075]=
MMF-301 [ ] X[0.000375]= [ ] X[0.000375]=
MMF-302 [ ] X[0.00027]= [ ] X[0.00027]=
MMF-302-6 [ ] X[0.00200]= [ ] X[0.00200]=
BG-12LX [ ] X[0.00023]= [ ] X[0.00023]=
CMF-300 [ ] X[0.00039]= [ ] X[0.00039]=
CMF-300-6 [ ] X[0.00225]= [ ] X[0.00225]=
CRF-300 [ ] X[0.00027]= [ ] X[0.00027]=
CRF-300-6 [ ] X[0.00145]= [ ] X[0.00145]=
I300 [ ] X[0.00040]= [ ] X[0.00040]=
ANN-80 [ ] X[0.0370]= [ ] X[0.0400]= [ ] X[0.0150]=
ANN-I/O [ ] X[0.0350]= [ ] X[0.2000]= [ ] X[0.0350]=
ANN-RLY [ ] X[0.0150]= [ ] X[0.0750]= [ ] X[0.0150]=
ANN-(R)LED [ ] X[0.0280]= [ ] X[0.0680]= [ ] X[0.0280]=
ANN-S/PG [ ] X[0.0450]= [ ] X[0.0450]= [ ] X[0.0450]=
NAC #1
5
[ ] X[ ]=
NAC #2 [ ] X[ ]=
Sum each column
6
for totals Primary Non-Alarm = Primary Alarm = Secondary Non-Alarm =
Table Footnote
1. If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
2. Refer to the Device Compatibility Document for standby current.
3. Must use compatible listed Power Supervision Relay.
4. Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
5. Current limitation of Terminal TB1 circuits is 2.5 amps total max.
6. Total current draw listed above cannot exceed 2.7 amps.