Programming
MS-9050UD PN 52413:C 01/23/08 61
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit
Detector Screen #2. This will cause the control panel to display the following Detector Type
Screen:
Pressing the down arrow key will display additional detector types as indicated in the following
table.
While viewing any Detector Type screen, select the type of detector being programmed by
pressing the corresponding keyboard number key. The display will return to Edit Detector
Screen #2 and indicate the selection next to the Type option.
Note: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory
point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the
fire alarm LED or alarm relay, if the detector senses smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector
Screen #2 so that the display reads Verification On. Each time the 3 key is pressed, the display
will toggle between Verification On and Verification Off. For a detailed description, refer to
"Alarm Verification (None or One Minute)" on page 158.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of
manually resetting the control panel after each device activation. To enable a device for the
Walktest feature, press 1 while viewing the Edit Detector Screen #3 until the display reads
Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and
Walktest No. Refer to "Walktest" on page 158.
Detector Type Action When Activated
Smoke Photo Fire Alarm
User-Defined-1 same as previous (Smoke Photo)
Smoke Ion Fire Alarm
User-Defined-2 same as previous (Smoke Ion)
Heat Detect Fire Alarm
User-Defined-3 same as previous (Heat Detect)
Smoke DuctP Fire Alarm
User-Defined-4 same as previous (Smoke DuctP)
Photo w/Heat Fire Alarm
User-Defined-5 same as previous (Photo w/Heat)
Duct Superv Supervisory, latching
User-Defined-6 same as previous (Duct Superv)
Photo Superv Supervisory, latching
User-Defined-7 same as previous (Photo Super)
future not used
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1
See Page
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3