Programming
72 MS-9050UD PN 52413:C 01/23/08
Monitor module type selection will affect the function of the point as follows:
Notes:
1. For entries ending in AR, AR refers to AutoResettable.
2. For HVAC RESTART AND HVAC OVRRIDE descriptions, refer to "HVAC Control" on
page 198.
3. Drill Switch Auto-Resettable turns on the NACs and any control module mapped to the Drill
Switch zone.
4. Conventional 2-wire smoke detectors may be powered using an external power supply with
an SLC Control Relay Module programmed for Resettable Power operation. A Control
Relay Module set to the Resettable Power type will follow the main circuit board 24 VDC
resettable power unless the control module is disabled.
5. Use only these Monitor Type IDs for the Zone Modules (MMF-302). The Zone Modules
will not function correctly if any other Type ID is used.
6. Combination systems employing these non-fire monitor types require the SLC loop to be
programmed by the installer for Style 4 operation and
isolator modules must be employed on
each non-fire branch of the SLC as per Figure 13 in the SLC Wiring Manual (document
number 51309). Fire and non-fire devices must not be used on the same SLC branch.
Table 3.1 Monitor Types
Monitor Type Action When Activated
Pull-Station Fire Alarm
User-Defined-1 Fire Alarm
Waterflow Fire Alarm Delayed (uses waterflow delay)
User-Defined-2 Fire Alarm Delayed (uses waterflow delay)
Monitor Fire Alarm
User-Defined-3 Fire Alarm
Future Use Future Use
Future Use Future Use
Smoke-Conventional
4, 5
Fire Alarm
User-Defined-5
5
Fire Alarm
Heat-Conventional
5
Fire Alarm
User-Defined-6
5
Fire Alarm
Medic-Alert
6
Supervisory, latching
User-Defined-7 Supervisory, latching
Hazard-Alert
6
Supervisory, latching
User-Defined-8 Supervisory, latching
Tornado-Alert
6
Supervisory, latching
User-Defined-9 Supervisory, latching
Future Use Future Use
Future Use Future Use
Tamper Supervisory, nonlatching (tracking)
User-Defined-11 Supervisory, nonlatching (tracking)
Supervisory Supervisory, latching
User-Defined-12 Supervisory, latching
Supervisory-AR
1
Supervisory, nonlatching (tracking)
User-Defined-13 Supervisory, nonlatching (tracking)
HVAC OVRRIDE Switch Supervisory, nonlatching (tracking)
Power-Monitor AC Fault
User-Defined-14 AC Fault
Trouble-Monitor Trouble
User-Defined-15 Trouble
Proc-Mon
6
Piezo
User-Defined-16 Piezo
Procmon-AR
1, 6
Piezo, nonlatching (tracking)
User-Defined-17 Piezo, nonlatching (tracking)
Future Use Future Use
Future Use Future Use
Ack-Switch Acts like panel Acknowledge Key
Sil-Switch Acts like panel Alarm Silence Key
Reset-Switch Acts like panel Reset Key
Drill-Switch Acts like panel Drill Key
PAS-Bypass PAS Disable
HVAC RESTART Switch
Drill-Switch AR
1
Acts like panel Drill Key, nonlatching (tracking)
3