LTE-I Installation and Setup Guide
22
PROMPTS OPTIONS DESCRIPTION
24
Supervision
(24 Hours)_
IP & Cell or Cell
Only:
None
30 Day
24 Hours
IP only:
None
30 Day
24 Hours
6 minutes
3 minutes
90 seconds
Additional options
for CN only.
1 Hr
3 Min
90 seconds
75 seconds
The AlarmNet network must hear at least one supervisory message
from the communicator during this supervision period; otherwise,
AlarmNet notifies the central station that a communication failure has
occurred. (If the supervision period is changed after registration, you
must re-register the communicator.)
Press the [space] key to scroll through choices.
UL: For IP + Cell set to 24 Hrs. For IP only set to 3 Min. For Cell only
set to 24 Hrs.
A loss of communications is treated as an Alarm condition.
ULC: Must be set to "CN UL Line Lvl 3" for ULC-S304 Active Level 3 or
ULC-S559 Active Fire installations. All other commercial applications
must be set to "24 Hrs".
25
Cell Rollover Y/N
(Y)_
[Y] , [N]
This prompt appears only if comm. path is set to IP & Cell.
If enabled, all messages (including AlarmNet network supervisory
messages) are sent over the cell network in the event of an Internet
failure.
If disabled, all messages (except AlarmNet network supervisory
messages) are sent automatically over the cell network in the event of
an Internet failure.
UL/ULC: Must be set to "Y" if 24 hours is selected in Prompt: 24:
Supervision. Must be set to "N" for ULC-S304 Active Level 3 or ULC-
S559 Active Fire installations where CN UL Line Lvl 3 is selected.
IMPORTANT WARNING: If set to "Y", AND Prompt 24: Supervision is
set to occur less than every 24 hours, this can result in data overage
charges on your monthly bill.
26
Cell 24Hr Tst Y/N
(N)_
[Y], [N]
This prompt appears only if comm. path is set to IP & Cell.
If enabled a message is sent every 24 hrs over Cell to verify proper
operation. If it fails, a Periodic Comm Test Failure message will be sent
over Ethernet.
UL/ULC: Must be set to "Y".
27
Old Alarm Time
10 Minutes_
10 Minutes
15 Minutes
30 Minutes
1 Hour
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
Sets how long an undeliverable alarm is retried for delivery to the
central station. If the message is not validated, it is retried until the old
alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
UL/ULC: Must be 10 minutes.
28
IP Flt Time
(60 mins)_
[00-99] This prompt appears only if comm. path includes IP.
In the event there is a loss of contact with the network over the Ethernet
connection, enter the time delay (in minutes) before the communicator
notifies the central station. IP failure will always be sent to the central
station as Primary Communication Path Failure.
UL/ULC: Must be one (01) minute.
29
Cell Flt Time
(60 mins)_
[00-99]
This prompt appears only if comm. path includes Cell.
In the event the communicator detects a communication path failure,
enter the time delay (in minutes) before the communicator notifies the
central station. A cell failure will always be sent to the central station as
Secondary Communication Path Failure.
UL/ULC: Must be one (01) minute.