ID3000/ID2000 Fire Panel Configuration Tool Manual
Loop Devices
3 - 13 997-291, Version 3.05
November 2010
SMART Sensors
The system supports Self-optimising Multi-
criteria Alarm Recognition Technology
(SMART) sensors.
SMART sensors have the following detection
capabilities:
- SMART 2 & SMART 3 sensors -
photoelectronic (optical), infra-red and
thermal. Learnt as type MULT.
- SMART 4 sensors - Carbon monoxide and
photoelectronic (optical), infra-red and
thermal. Learnt as type SMART 4.
All SMART sensors have a thermal-only mode
as described on the previous page for
Optiplex. SMART 4 has a unique device type,
unlike Optiplex/SMART 2/SMART 3, which
are type MULTI with a thermal-only mode
(alarm level 6; when the thermal-only mode
is selected the type is automatically changed
to ‘Optiplex’).
The Alarm and Pre-alarm levels and defaults
are as described for Optiplex, and the
verification delays are the same as for a
MULTI sensor.
The maintenance status of SMART 4 sensors
is stored in a log and can be retrieved using
the Historic and Data Log Tool as described
in Appendix 1.