44 UDACT Instruction Manual — P/N 50050:M 12/18/2009
Programming Instructions Programming Reference Sheets
59 Make/Break Ratio: If rotary dialing is selected in Address 58; Enter “0” for a 67/73
make/break ratio; “1” for a 62/38 make/break ratio.
60 Leave default of 0.
61 Leave default of 0.
62 AC Loss Reporting Delay: Enter “0” for no time delay after AC loss; “1” for 1 hour
delay; “2” for 2 hour delay (factory default); “3” for 6 hour delay; “4” for 7 hour delay; “5” for 8
hour delay; “6” for 9 hour delay; “7” for 10 hour delay; “8” for 11 hour delay; “9” for 15 hour
delay; “A” for 16 hour delay; “B” for 17 hour delay; “C” for 20 hour delay; “D” for 21 hour delay;
“E” for 22 hour delay; or “F” for 23 hour delay.
63 Host Panel ID: Enter ”0” for AFP-100; “1” for System 500; “3” for System 5000; “4” for
System 5000 with AIM-200; “5” for NFS2-640, NFS-640, and NFS-320; “7” for
AM2020/AFP1010, NCA-2, NCA, NFS2-3030, and NFS-3030; “8” for AFP-300/AFP-400; or
leave default of “6” for AFP-200; all other entries are invalid.
64 65 Loop Number: Factory set to “00”. Valid entries are 00 through 97
66 67 68 Device/Zone Number for General Reports: Factory set to “000”. Valid
entries are 000 through 999.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER UDACT and is the answer not in the manual?

Honeywell NOTIFIER UDACT Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER UDACT
CategoryCell Phone
LanguageEnglish

Related product manuals