UDACT Instruction Manual — P/N 50050:M 12/18/2009 43
Programming Reference Sheets Programming Instructions
3.8 Programming Reference Sheets
3.8.1 Options
To enter Programming, press MODE, then 7764, then ENTER/STORE.
00 01 02 03 04 05 06 07 08 09 10 11 12
13 14 15 Primary Phone Number: Enter 'F' to represent the end of the number.
16 Primary Communication Format: Enter 0 - F.
1718 19 20 Primary Account Code: Valid keys are 0-F.
21 22 23 24 Primary 24-Hour Test Time: Enter military time (i.e. 1400 for 2
PM).
25 Primary Number Test Time Interval: Enter “0” for 24-hour; “1” - 12-hour.
26 27 28 29 30 31 32 33 34 35 36 37 38
39 40 41 Secondary Phone Number: Enter “F” to represent the end of the number.
42 Secondary Communication Format: Enter 0-F.
43 44 45 46 Secondary Account Code: Valid keys are 0-F.
47 48 49 50 Secondary 24-Hour Test Time: Enter military time (1400 for 2
PM).
51 Secondary Number Test Time Interval: Enter “0” for 24-hour; “1” - 12-hour.
52 53 Start Monitoring Address: Valid entries are 01 through 32.
54 55 End Monitoring Address: Valid entries are 01 through 32.
56 UDACT Communication Selection: Enter “0” to disable UDACT communication; “1”
for zone reporting receive only communication; “2” for zone reporting receive/transmit
communication; “3” for point reporting receive only; or “4” for point reporting receive/transmit.
57 Backup Reporting: Enter “0” to have secondary phone number act as backup only; “1” to
have secondary phone number receive all reports and messages along with primary phone number.
58 Touchtone/Rotary Select: Enter “0” for touchtone dialing; “1” for rotary dialing.
Continued on the next page...