Section 1: Overview
1.1 Introduction
This document contains information for installing, programming and operating the UDACT,
Universal Digital Alarm Communicator/Transmitter.
1.2 UL 864 Compliance
1.2.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in
retrofit applications. Operation of the UDACT with products not tested for UL 864 9th Edition has
not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These
applications will require the approval of the local Authority Having Jurisdiction (AHJ).
1.2.2 Programming Features Subject to AHJ Approval
This product incorporates field-programmable software. The features and/or options listed below
must be approved by the local AHJ.
System 500 NFS-640
System 5000 NCA
AM2020/AFP1010 AFP-300/400
AFP-100 NFS-3030
AFP-200
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control
Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not
used at all as indicated below.
Program Feature or Option Permitted in UL 864? (Y/N) Possible Settings Settings Permitted in UL 864
AC Loss Reporting Delay YES 1 = 1 hour
2 = 2 hour
3 = 6 hours
4 = 7 hours
5 = 8 hours
6 = 9 hours
7 = 10 hours
8 = 11 hours
9 = 15 hours
A = 16 hours
B = 17 hours
C = 20 hours
D = 21 hours
E = 22 hours
F = 23 hours
1 = 1 hour
2 = 2 hour
Host Panel ID YES 0 = AFP-100
1 = System 500
2 = Do not use
3 = System 5000
4 = System 5000 with AIM-200
5 = NFS2-640, NFS-640, NFS-
320
6 = AFP-200
7 = AM2020/AFP1010, NCA,
NCA-2, NFS-3030, NFS2-3030
8 = AFP-300/AFP-400
9 = Do not use
5 = NFS2-640, NFS-320
7 = NCA-2, NFS2-3030

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER UDACT and is the answer not in the manual?

Honeywell NOTIFIER UDACT Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER UDACT
CategoryCell Phone
LanguageEnglish

Related product manuals