Introduction
January 09 UDA2182 Communications User Guide 1
1. Introduction
1.1 Overview
The UDA2182 provides Modbus communications support on two communication interfaces using the
optional Communication Card.
Serial port provides
RS422/RS485 multi-drop
2400 to 115200 programmable baud rate
Modbus RTU protocol to read signals including PV, Temperature, Alarm Status, outputs, relay
status, etc.
Read/write four analog and four digital variables (Note 1)
Can communicate to the P.IE. tool
Ethernet port provides:
Up to 5 Modbus TCP connections simultaneously
Ethernet parameters are configured via the front-panel or web pages.
Web server with up to 10 clients simultaneously
Web pages (Note 2) setup the Ethernet port settings and monitor readings, alarms, statuses,
events. See Section 12
Multi-language email to send alarm status changes. Alarm notification to eight email addresses.
These must be configured using web pages signed in as the administrator.
DHCP: ( Dynamic Host Configuration Protocol) selectable via web page or front-panel
Firmware upgrade to Main CPU board
Firmware upgrade to Communications card
Can communicate to the P.IE. tool
Note 1
There are four analog and four digital variables. These variables can be read and written remotely using
Modbus function codes.
Variables will appear as a selection for various parameters:
Analog variables can be an alarm source, analog relay source, current output source, monitor
source, math source, auxiliary switch source, PID TRV, and PID remote setpoint.
Digital variables can be an alarm disable, remote setpoint select, Tune Set2 select, digital relay
source, logic-in source, auxiliary switch select, PID TRC select, PID RSP select, and auto cycle
start source.
Note 2
Web pages (Section 12) provide the following:
Multiple language support
“Guest” accessibility for read-only permission
“Admin” accessibility for read and write permission
Readings of Inputs, Outputs, and Relay Outputs
Status of Inputs, Outputs, and Alarms.
Readings and Status of optional parameters (control, pharma, and auto-cycle)
List of last twelve events
Network configuration including IP address, subnet mask, gateway etc.
Email configuration for alarm event notification

Table of Contents

Other manuals for Honeywell UDA2182

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDA2182 and is the answer not in the manual?

Honeywell UDA2182 Specifications

General IconGeneral
BrandHoneywell
ModelUDA2182
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals