Table 39 EVA6x00 power specifications — 230 Volts
2C8D2C7D2C6D2C5D2C4DSpecification
33442967259022141837Total System
Wattage
Typical
1
1140910124883875536268Total System
BTU/hour
7.97.06.15.24.3Input Current (A) -
Typical per line
403357311272244In Rush Current (A)
13.311.910.08.87.3Input Current (A) -
Maximum per line
Failover Mode
1 Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly.
For example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K
RPM drives.
Table 40 EVA8x00 power specifications — 208 Volts
2C12D2C10D2C8D2C6D2C2DSpecification
49204167341426601153Total System
Wattage
Typical
1
16789142181164890773936Total System
BTU/hour
12.310.48.56.72.9Input Current (A) -
Typical per line
528451363280132In Rush Current (A)
20.817.714.511.34.9Input Current (A) -
Maximum per line
Failover Mode
1 Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly.
For example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K
RPM drives.
Table 41 EVA8x00 power specifications — 230 Volts
2C12D2C10D2C8D2C6D2C2DSpecification
49204167341426601153Total System
Wattage
Typical
1
16789142181164890773936Total System
BTU/hour
11.69.88.16.32.7Input Current (A) -
Typical per line
586500403311147In Rush Current (A)
19.716.713.710.64.6Input Current (A) -
Maximum per line
Failover Mode
1 Typical is described as a system in normal steady state operation. (i.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly.
For example, if you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K
RPM drives.
Storage system specifications 121

Table of Contents

Other manuals for HP 6100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP 6100 and is the answer not in the manual?

HP 6100 Specifications

General IconGeneral
BrandHP
Model6100
CategoryStorage
LanguageEnglish

Related product manuals