AC power - PDU options
HP XP7 is configured for input power using separate rackmount PDU products. PDUs are available
for three phase or single phase power for NEMA and IEC compliance applications.
Table 26 HP XP7 AC PDU options
Notes
Facility
receptacle
neededPlug Type
Branch circuit
requirements
per PDU
Number of
PDU per Rack
1
Local Power
Product
Number
For customers
with, 200 - 220
NEMA
L15-30R
NEMA
L15-30P
200-220V, 3Ø,
4-wire, 30A
23 phase (4
wire)
H6F71A
VAC, 3-Phase,
4-Wire Power
Distribution
System
For customers
with 380 - 415
IEC60309 4
pole, 5-wire,
IEC60309 4
pole, 5-wire
380-415V, 3Ø,
5-wire, 16A
23 phase (5
wire)
H6F73A
VAC,380-415 VAC,
16A
380-415VAC,
16A Three-Phase,
5-Wire Wye
Power
Distribution
System
For customers
with single
NEMA L6-30RNEMA L6-30P200-240V, 1Ø,
3-wire, 30A
4single phase
NEMA
H6F70A
phase power
and need
NEMA L6-30P
plug
For customers
with single
IEC60309 2
pole, 3-wire,
240VAC, 32A
IEC60309 2
pole, 3-wire,
240VAC, 32A
200-240V, 1Ø,
3-wire, 32A
4single phase
IEC
H6F72A
phase power
and need
IEC60309 32A
plug
Notes
1. Each PDU has one fixed power cord with attached plug. Power cord is not removable.
NOTE: PDU models can be changed in the field using offline maintenance procedures.
NOTE: When ordering systems, HP does not allow mixtures of different phase PDUs in a system
(even though there are no technical issues). Only upgrade orders can ship with difference phase
PDUs in a system.
80 Specifications