UPS power rating Upstream circuit breaker
5000VA D curve—30A
6000VA D curve—32A
• Recommended cable cross-sections
Terminal position Wire function Terminal wire size
rating
Minimum input
sire size
Tightening torque
L1 Phase 4-16mm
1
(12-6AW
G)
6mm
1
(10AWG)
105°C (221°F)
10lb in/1.13 Nm
N (L2) Neutral (phase) 10mm
1
(8AWG)
75°C (167°F)
Ground
1
Copper wire, solid, or stranded.
Connecting the Input/Output
WARNING: Hewlett Packard Enterprise recommends that this connection is made only by a licensed
electrician.
20 Installation