Description Chassis Number of LFF/SFF/NVMe
drives that correspond to
the server
Maximum inlet ambient
temperature
Apollo r2800
Gen10 Chassis
with SAS Expander
0 to 24 drives
Using an optical cable: 25°C
(77°F)
Using a copper cable: 35°C
(95°F)
NIC cards with
SFP+, SFP28 or
QSFP transceiver /
InfiniBand adapters
with QDR or FDR
speed
Apollo r2800
Gen10 Chassis
with 16 NVMe
0 to 4 drives
Using an optical cable: 25°C
(77°F)
Using a copper cable: 35°C
(95°F)
NIC cards with
QSFP28
transceiver /
InfiniBand adapters
with EDR speed
Apollo r2200
Gen10 Chassis
3 drives
Using an optical cable: not
supported.
Using a copper cable: 25°C
(77°F)
Apollo r2200
Gen10 Chassis
0 to 2 drives
1
Using an optical cable: 22°C
(71.6°F)
Using a copper cable: 35°C
(95°F)
Apollo r2600
Gen10 Chassis
0 to 6 drives
Using an optical cable: 22°C
(71.6°F)
Using a copper cable: 35°C
(95°F)
Apollo r2800
Gen10 Chassis
with SAS Expander
0 to 24 drives
Using an optical cable: 22°C
(71.6°F)
Using a copper cable: 35°C
(95°F)
Apollo r2800
Gen10 Chassis
with 16 NVMe
0 to 4 drives
Using an optical cable: 22°C
(71.6°F)
Using a copper cable: 35°C
(95°F)
1
If the component is installed in server 1 or server 2, and the server is installed in the Apollo r2200 Gen10 Chassis,
drive blanks must be installed in drive bays 1-2 and 2-2. Similarly, if the component is installed in server 3 or server 4,
and the server is installed in the Apollo r2200 Gen10 Chassis, drive blanks must be installed in drive bays 3-2 and
4-2. For more information, see Drive blank installation guidelines for the HPE ProLiant XL170r Gen10 Server.