DIMMs
Description Chassis Fan configuration Number of LFF/SFF/
NVMe drives that
correspond to the
server
Maximum inlet
ambient temperature
32 GB
RDIMM
Apollo r2200
Gen10
Chassis
Redundant (8 fans) 3 drives 30°C (86°F)
Apollo r2200
Gen10
Chassis
Redundant (8 fans) 0 to 2 drives
1
35°C (95°F)
64 GB
LRDIMM
Apollo r2200
Gen10
Chassis
Redundant (8 fans) 3 drives This configuration is
not supported.
Apollo r2200
Gen10
Chassis
Redundant (8 fans) 0 to 2 drives
1
35°C (95°F)
128 GB
LRDIMM
Apollo r2200
Gen10
Chassis
Redundant (8 fans) 3 drives This configuration is
not supported.
Apollo r2200
Gen10
Chassis
Redundant (8 fans) 0 to 2 drives
1
30°C (86°F)
Apollo r2600
Gen10
Chassis
Redundant (8 fans) 0 to 6 drives 30°C (86°F)
1
If the component is installed in server 1 or server 2, and the server is installed in the Apollo r2200 Gen10 Chassis,
drive blanks must be installed in drive bays 1-2 and 2-2. Similarly, if the component is installed in server 3 or server 4,
and the server is installed in the Apollo r2200 Gen10 Chassis, drive blanks must be installed in drive bays 3-2 and
4-2. For more information, see Drive blank installation guidelines for the HPE ProLiant XL170r Gen10 Server.
Storage controllers
Description Chassis Number of LFF/SFF/NVMe
drives that correspond to
the server
Maximum inlet ambient
temperature
HPE Smart Array
P408i-p Controller
1
Apollo r2200
Gen10 Chassis
3 drives 22°C (71.6°F)
Apollo r2200
Gen10 Chassis
0 to 2 drives
2
30°C (86°F)
Apollo r2600
Gen10 Chassis
0 to 6 drives 28°C (82.4°F)
Apollo r2800
Gen10 Chassis
with SAS Expander
0 to 24 drives 28°C (82.4°F)
Table Continued
DIMMs 91