EasyManua.ls Logo

Huawei FusionDC1000A - Heat Detector

Huawei FusionDC1000A
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 7-7 Smoke sensor
Table 7-3 Smoke sensor specications
Item Specications
Operating voltage 9–33 V DC
Quiescent current 30–50 μA at 24 V
Alarm current 52 mA at 24 V
Output mode Relay output
Operating temperature –20ºC to +60ºC
Ambient humidity 0%–95% RH (non-condensing)
Dimensions Diameter: ≤ 112 mm; height: 50 mm (with a
base)
7.5 Heat Detector
The detector measures the onsite temperature in real time. When the detector
works in monitoring mode, the red indicator blinks and the operating current is
low. When the onsite temperature exceeds the alarm threshold, the detector
enters alarm mode, the red indicator is steady on, and the circuit current increases
rapidly. The detector issues an alarm signal in the form of circuit current change,
and provides the alarm locking function. The alarm can be reset only by short-
time power-o.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 7 Fire Extinguishing System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 106

Table of Contents

Other manuals for Huawei FusionDC1000A

Related product manuals