Item Specications
Sound pressure level 95–115 dB (within 1 m in front)
Operating
temperature
–20°C to +55°C
Operating humidity 5%–95% RH
7.9 Extinguishant Abort Button
If a re occurs in the pre-fab. module, the extinguishant control panel drives the
electrical actuator to start the re extinguisher to release the extinguishant.
During the delay period, if onsite personnel conrm that there is no re in the
protected area, they can press the abort button immediately to interrupt the
extinguishant release delay and disable the extinguishant release drive signal
output to prevent extinguishant release.
Figure 7-12 Extinguishant abort button
Table 7-8 Technical specications of the extinguishant abort button
Item
Specications
Dimensions (H x W x D) 150 mm x 130 mm x 85 mm
Operating temperature –5°C to +40°C
Relative humidity ≤ 95% RH
Operating voltage 30 V DC
Operating current 2.5 A
7.10 Fire Alarm Horn Strobe
The device can generate audible alarm signals after being connected to a 24 V DC
power supply. It can be used with a re alarm control panel through an output
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 7 Fire Extinguishing System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 110