Item Specications
Water supply requirements The inlet water pressure should be in the range of 0.1–0.7 MPa (a
reducing valve must be installed at the humidier water inlet if the
inlet water pressure exceeds 0.7 MPa), and the temperature should
be in the range of 1°C–40°C.
The wet lm humidier uses tap water and does not require an
additional water treatment device at the water inlet. The water
requirements are as follows:
Non-freezing and nephelometric turbidity units (NTU) < 3
No visible substances
6.5 ≤ pH value ≤ 8.5
Total hardness (in CaCO3) ≤ 450 mg/L
Drainage requirements The distance between the top drainage of the water pump and the
cabinet installation oor should not exceed 4 m.
Power distribution
requirements
Leakage circuit breakers are not recommended for the main power
supply route. If a leakage circuit breaker is required by the customer
or local regulations, select the residual current circuit breaker
(RCCB) that is insensitive to single-phase DC pulsation and transient
impulse current.
Note: If certain conditions are not met, contact Huawei technical support.
5.2.3 Technical Specications
Table 5-5 General specications
Item
Specications
Cooling mode Air cooled
Refrigerant R410A
Air ow mode Horizontal air ow
Dimensions (H
x W x D)
2000 mm x 300 mm x 1100 mm (cabinet)
Net weight 230 kg
Environmental
friendliness
REACH, RoHS
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 5 Cooling System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 55