Item Technical Specications
Installation space ● 42 U available space
● The distance between the front and rear
mounting bars can be adjusted for every 25
mm.
– For a 1200 mm deep cabinet: The
maximum depth for installing devices
inside the cabinet is 750 mm and can be
extended to 850 mm by adjusting the
mounting bars.
– For a 1100 mm deep cabinet: The
maximum depth for installing devices
inside the cabinet is 700 mm and can be
extended to 750 mm by adjusting the
mounting bars.
– If the depth of the equipment exceeds
the specications, the cabinet needs to
be customized by raising RM
requirements.
● Positions for vertically installing two rPDUs
are provided in the rear of the cabinet.
Installation mode
Supports installation on a base and raised
oor.
Door opening mode The front door is a single door, and the rear
door is a double one.
Weight of an empty cabinet ● 2000 mm x 600 mm x 1100 mm: 110 kg
● 2000 mm x 600 mm x 1200 mm: 130 kg
NOTE
The weight of an empty cabinet includes the weight
of the front and rear doors.
IP rating IP20
3.6.4 Raised Floor
The raised oor is installed at the smart cooling product side to facilitate pipe
routing for smart cooling products.
● The raised oor consists of ooring, legs, beams, and conductive rubber pads.
● The oor does not dislocate or deform after long range transportation, and is
easy to assemble and maintain.
● The legs can be adjusted in height, and are galvanized to provide ecient
anti-corrosion performance.
● The compression strength of both the raised oor and legs is greater than
1500 kg/m
2
.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 3 Structural system
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 17