3.4 Pre-fab. Module Doors
Figure 3-3 Fireproof door
Table 3-1 Fireproof door technical specications
Fireproof Door
End Door (Main
Entrance)
Device Installation
Door/Emergency Door
Fire resistance time 90 min
Width 1100 mm
Net height 2420 mm
IP rating IP65
Door opening angle ≥ 120°, congured with a door closer
Bearing capacity When the door is open, the door, door frame, and
mechanical parts can withstand the door weight and
will not deform permanently within 48 hours with a
static load of 15 kg at any part.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 3 Structural system
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 12