Loading...
No. Silk Screen Port Name Description
9 EPO NO EPO port If the normally open (NO) signal
port is connected to the EPO_12V
port, emergency power-o (EPO)
is triggered.
12V
NC If the normally closed (NC) port
is disconnected from the EPO_12V
port, EPO is triggered.
12V
10 DI_1 Input dry
contact
Reserved
11 DI_2 Input dry
contact
Reserved
NO TICE
In a parallel lithium battery system, activating the EPO signal of a single lithium
battery cabinet triggers only EPO of this cabinet, and does not aect normal
charge and discharge of other lithium battery cabinets in the system.
Table 4-11 Port and pin denitions
Appearance
Pin COM Port RS485 Port FE Port
1 RS485_T+ RS485_T+ RJ_TX+
2 RS485_T RS485_T RJ_TX–
3 - - RJ_RX+
4 RS485_R+ RS485_R+ -
5 RS485_R RS485_R -
6 GND GND RJ_RX
7 - - -
8 - - -
4.5.3 BCU
The BCU is swappable and supports power conversion, current equalization, and
BCU (intra-cabinet BMS) management.
Converts the power of battery strings. When the consistency between battery
strings is poor, the BCU controls the current balance between battery strings
through voltage boosting and balance adjustment to implement active
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 4 Power Supply and Distribution System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 37