EasyManua.ls Logo

Huawei FusionDC1000A - Page 66

Huawei FusionDC1000A
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 5-15 Dimensions of the NetCol500 outdoor unit
Table 5-10 Technical specications of the NetCol500 outdoor unit
Product Model NetCol500-A040MS1E0
Power supply Powered by the indoor unit
Indoor unit model NetCol5000-A025
Operating temperature range –20°C to +55°C (–40°C to +45°C with a low temperature
component)
Fan speed range 10%–100%
Number of fans 1
Dimensions H1 (H2) x W1 (W2) x D
(mm)
1096 (665) mm x 1120 (984) mm x 1094 mm
Liquid pipe outer diameter 5/8 inch (15.9 mm)
Gas pipe outer diameter 3/4 inch (19.1 mm)
Certication RoHS, REACH, CE
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m, derated at above 1000 m. For details about
derating data, contact Huawei technical support.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 5 Cooling System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 59

Table of Contents

Other manuals for Huawei FusionDC1000A

Related product manuals