Figure 6-1 Management system networking diagram
● Common card readers are congured for the access control system by default, and they
should be used at an ambient temperature ranging from –40°C to +85°C. Customized
three-in-one ngerprint and card readers with keypads are also supported, and they
should be used at an ambient temperature ranging from –10°C to +55°C. The three-in-
one card readers cannot be used outdoors when the ambient temperature is below –
10°C or exceeds 55°C.
● The camera uses an SD card with a capacity of 64 GB for storage by default, and
supports 7x24 recording at 720P/512K. A video management device (IVS) should be
congured if there is a need of longer-time storage, management, and conguration of
external cameras.
● Scenario without an IVS: Connect the signal cables of the indoor and outdoor cameras
to the PoE ports on the smart ETH gateway.
● Scenario with an IVS: Connect the signal cables of the indoor and outdoor cameras to
the LAN switch.
Table 6-1 Management system congurations
Function
ECC800-Pro NetEco
Client
authorization
16 PCS One license manages up to 25 smart nodes.
Work order
management
No Yes
Energy eciency
management
Yes Yes
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 6 Management System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 64