Item Specications
PAD
intelligent
charging
Charging stops when the PAD battery level reaches 100%. When
the battery level is lower than 40% (default value, which can be
set to 30, 40, or 50), charging starts.
BLINK
button
● Press the button for less than 1 second to start blinking.
● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.
Indicators
Table 6-25 AC actuator indicators
Indica
tor
Color Name Status Description
Power Green Power status
indicator
Steady on The power input is normal.
O There is no power input.
RUN Green Running
status
indicator
O The power is abnormal or the
board program is loading.
Blinking at
long
intervals
The AC actuator successfully
registers with the ECC800-Pro
and the software runs properly
(the indicator blinks at 0.5 Hz,
on for 1s and then o for 1s).
Blinking at
short
intervals
The communication fails or
the AC actuator fails to
register with the ECC800-Pro
(the indicator blinks at 4 Hz,
on for 0.125s and then o for
0.125s).
Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then o for 0.05s)
and then turns o for 0.5s.
The cycle lasts for 5s.
ALM Red Alarm
indicator
Steady on A system failure alarm is
generated.
O No system alarm is generated.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 6 Management System