(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand interface (9) WG_1 Wiegand interface
(10) AI/DI_2 dry contact
(reserved port for linkage
control or third-party re
extinguishing system dry
contacts)
(11) AI/DI_1 dry contact
(reserved port for exit
button)
(12) LOCK/GND/GATE/COM door
status sensor and magnetic lock
port
Specications
Table 6-26 Access actuator technical specications
Item Specications
Power input ● DC input: terminal, with an input voltage of 36 V DC–60 V DC
● PoE power supply: one PoE port that complies with
IEEE802.3at
PoE port FE communication with the rate of 10/100 Mbit/s
Wireless
communicat
ion
One wireless communication port that complies with IEEE
802.15.4, mutual backup with FE communication
AI/DI port Two AI/DI ports, can connect to the re alarm and exit button
DO/DI port ● One 12 V DC power output that controls magnetic locks,
terminal
● One DI input port for connecting to the door status switch
RS485 serial
port
expansion
Two RS485 ports (one route) with the default communication
rate of 9600 bit/s, physical port cascading supported (reserved
function)
Wiegand
port
Two Wiegand ports, 12 V DC card reader operating power output;
two routes of card readers can operate at the same time.
BLINK
button
● Press the button for less than 1 second to start blinking.
● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.
Address DIP
switch
4-pin address DIP switch