FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Figure 3-62 Water sensor and water detection cable
Table 3-56 Technical specifications of a water sensor
Output when no liquid exists
Output when liquid exists
–20°C to +70°C, 10%–80%RH
(non-condensing)
–40°C to +80°C, 10%–80%RH
(non-condensing)
Default length of the water detection cable
The water detection cable can connect to the
quick-connect terminal and can be extended
flexibly to 50 m at most.
Reliability of the water detection cable
The water detection cable cannot be
installed on the surface of metal.
3.4.9 (Optional) Smoke Detector
Smoke detectors are used to detect smoke in the aisle containment.
Figure 3-63shows a smoke detector. Table 3-57 lists its technical specifications.