7 Installation and Configuration
7.1 Installation Environment Requirements
7.2 Hardware Installation
7.3 Power-On and Power-Off
7.4 Initial Configuration
7.1 Installation Environment Requirements
7.1.1 Space and Airflow Requirements
To allow for servicing and adequate airflow, observe the following space and airflow
requirements:
l Install the server in an access-restricted area.
l Keep the area in which the server is located clean and tidy.
l To facilitate heat dissipation and maintenance, keep a clearance of 800 mm (31.50 in.)
between walls and the front and rear doors of the cabinet.
l Do not block the air intake vents. Otherwise, air intaking and heat dissipation will be
affected.
l The air conditioning system in the equipment room provides enough wind to ensure
proper heat dissipation of all components.
FusionServer Pro 2288H V5 Server
User Guide
7 Installation and Configuration
Issue 08 (2019-10-30) Copyright © Huawei Technologies Co., Ltd. 73