EasyManuals Logo

Huawei SUN2000-3KTL-L1 User Manual

Huawei SUN2000-3KTL-L1
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
NO TE
Ensure that the baud rates of the DDSU666-H and YDS70-C16 meters are set to
the default values. If they are changed, meters may go oine, generate alarms, or
aect the inverter output power.
The preceding networking uses DDSU666-H as an example. Cable connections for
other meter models may vary.
In cascading scenarios, the inverters are required to connect to the management
system through a Smart Dongle.
In the preceding networking, the SUN2000s are cascaded and support the grid-tied
point control function to achieve zero export.
If the SUN2000s requires the grid-tied point control function, they need to be
connected to a smart power sensor.
A single-phase power meter is recommended for the networking with only single-
phase inverters.
If the SUN2000-(2KTL-6KTL)-L1 are cascaded with three-phase inverters, they must
be connected to the grid in the same phase.
Only one LG battery is supported, and the LG battery must be connected to the
inverter equipped with the Smart Dongle.
LG batteries cannot be connected in cascading scenarios.
Procedure
Step 1 Connect signal cables to corresponding signal connectors.
NO TICE
Ensure that the protection layer of the cable is in the connector. The surplus
core should be cut
o from the protection layer.
Ensure that the exposed core is totally inserted into the cable hole.
Ensure that the signal cables are connected securely.
Ensure that the cables are not twisted.
If multiple signal cables need to be connected to a single connector, ensure
that the outer diameters of the signal cables are the same.
Figure 5-23 Crimping two signal cables
SUN2000-(2KTL-6KTL)-L1
User Manual 5 Electrical Connection
Issue 10 (2023-02-13) Copyright © Huawei Technologies Co., Ltd. 62

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-3KTL-L1 and is the answer not in the manual?

Huawei SUN2000-3KTL-L1 Specifications

General IconGeneral
Max. efficiency98.4%
Max. input voltage600 V
Nominal output power3000 W
Dimensions (W x H x D)365 x 365 x 156 mm
Operating temperature range-25°C to +60°C
Nominal AC voltage220 V / 230 V / 240 V
MPPT voltage range90 V - 560 V
Rated input voltage360 V
Number of MPPTs2
CoolingNatural Convection
Protection degreeIP65
Rated output voltage220 V / 230 V / 240 V
Output frequency50 Hz / 60 Hz
Power factor0.8 leading ... 0.8 lagging
THDi<3%
Efficiency98.4%
Warranty10 years
Max. apparent AC power3300 VA
Max. output power3300 W