Parameter Description
Maximum
protection time
- Species the time for detecting meter
data. If the Dongle does not detect
any meter data within the preset
time, the Dongle delivers the preset
value of the Active power output
limit for fail-safe to the inverter for
protection.
Power raising
threshold
- Species the threshold for raising the
inverter output power.
Communication
disconnection
fail-safe
Disable
Enable
In the inverter anti-backfeeding
scenario, if this parameter is set to
Enable, the inverter will derate
according to the active power
derating percentage when the
communication between the inverter
and the Dongle is disconnected for a
period longer than Communication
disconnection detection time.
Communication
disconnection
detection time
- Species the time for determining
the communication disconnection
between the solar inverter and the
Dongle.
Active power
output limit for
fail-safe
- Species the derating value of the
inverter active power by percentage.
If the Dongle does not detect any
meter data or the communication
between the Dongle and the inverter
is disconnected, the Dongle delivers
the derating value of the inverter
active power by percentage.
Power-
limited grid
connected
(kW)
Closed-loop
controller
SDongle/
SmartLogger
Inverter
Set this parameter to SDongle/
SmartLogger when the
SmartLogger1000A is connected.
If multiple inverters are cascaded,
set this parameter to SDongle/
SmartLogger.
If there is only one inverter, set
this parameter to Inverter.
SUN2000-(3KTL-10KTL)-M0
User Manual C Setting Export Limitation Parameters
Issue 06 (2020-10-23) Copyright © Huawei Technologies Co., Ltd. 93

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000 M0 Series and is the answer not in the manual?

Huawei SUN2000 M0 Series Specifications

General IconGeneral
Rated AC Output Power3000W
European Efficiency96.7%/97%/97%/97.3%/97.5%/97.8%
CommunicationRS485, Wi-Fi
Protection DegreeIP65
Weight17 kg
Dimensions440 x 650 x 220 mm
Max. efficiency98.6%
MPPT voltage range200-1000V
No. of MPPTs2
Operating temperature range-25°C to +60°C
Cooling methodNatural convection
Protection ratingIP65
AC output voltage230V