Status 21.08.2015 HYDAC ELECTRONIC GMBH Part No. 669850
12 Messages
12.1 ERROR MESSAGES
If an error is detected, a corresponding error message appears that must be
acknowledged by pressing any key.
Possible error messages:
E.01 The switch points and hysteresis values have been set in such a way that the
resulting switch-back point is no longer within the permitted setting range.
Example:
Switching point has been set to 8.20 inch, the hysteresis to 9.05 inch.
Action: Correct the settings.
E.10 A data error was detected in the saved settings. This could be due to strong
electromagnetic interference or a component fault.
Action: Check all settings (programming enable, switch points, switch-back points and
basic settings) and correct them, if necessary. If the error occurs frequently,
please contact the HYDAC Service Department.
E.20 Implausible measuring values have been reported from the level sensor for a long
period.
Action: Acknowledge the error message by pressing any key. If the error message
continues to be displayed, please contact our service department.
E.21 A communication error was detected within the level sensor.
Action: Acknowledge the error message by pressing any key. If the error message
continues to be displayed, please contact our service department.
E.22 An internal communication error to the temperature sensor (optional) was
detected.
Action: Acknowledge the error message by pressing any key. If the error message
continues to be displayed, please contact our service department.