62 MX3630-01 Rev. J SlideDriver/SlideDriver 50VF Series © 2019 www.hysecurity.com
Installer Menu Setting Options Menu Tasks & Explanations STC Wire
Connections
LO 0
LEAF DELAY OPEN
0 = none
1 through 20 in ½
second increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if gate operator is set up as a
Primary or a Secondary. Available settings
are 1 through 20. Each increment adds ½
second time delay following a command to
open before operator activates. Provides up
to a 10 second time delay.
RT 0 (60 SECS)
MAXIMUM RUN
TIME
0 = 60 Seconds max run
1 = 300 Seconds max run
Assigns a motor run time of 60 or 300
seconds. If the gate opening or closure takes
longer than 60 seconds, you’ll need to set
the run timer to 1.
N/A
PO 0 (OFF)
PARTIAL OPEN
0 = none
7 to 99 seconds
Sets distance (from closed gate position)
where gate stops if the partial open input
is activated. When a number is entered in
PO display, open partial input becomes
operational.
Open Partial
#6
COM
EC 0 STOP ONLY
EYE CLOSE LOGIC
0 = Close eye stops only
1 = Two second reversal to open
2 = Reverse to full open.
Default setting is non-reversal if close photo
eye is triggered while closing. A setting of 1
causes gate to reverse toward open for two
seconds if triggered while closing. A setting
of 2 reverses the gate to full open.
.Sensor 1, 2, or 3
Sensor COM
COM
+24V
EO 0 STOP ONLY
EYE OPEN LOGIC
0 = Open eye stops only
1 = Two second reverse to close
Default setting is non-reversal if open photo
eye is triggered while opening. A setting of 1
causes gate to reverse travel and close
for two seconds if triggered while
opening.
Sensor 1, 2, or 3
Sensor COM
COM
+24V
GR 0 FULL OPEN
GATE EDGE LOGIC
0 = Edge reverses fully open
1 = Two second reversal only
Default setting is a full-open reversal if gate
edge is triggered while closing. Optional
setting of 1 causes gate to reverse for two
seconds if triggered while closing.
Sensor 1, 2, or 3
Sensor COM
+24V
10K resistor
(Edge)
SR 1 REVERSE 25
REVERSAL LOGIC
0 = IES reverses fully open
1 = Two second reversal only
Default setting is a two-second duration
reversal if inherent sensor is triggered.
Optional setting of 0 will cause gate to
reopen fully if triggered while closing.
N/A
S1 0
SENSOR #1 TYPE
0 disabled
1 (NOT USED)
2 (EYE CLOSE)
3 (EDGE CLOSE)
4 (EYE OPEN)
5 (EDGE OPEN)
6 (EDGE BOTH)
7 (EYE BOTH)
UL 325 - 2018 sensor input setting for
external entrapment protection sensor
monitoring. All three sensor types must be
congured to a non-zero number before the
gate operator will move the gate. Edge
Both is only available in Swing Gate operator
types. Eye Both is only available in Slide
Gate operator types.
SENSOR 1
COM
+24V
SENSOR COM
10K resistor *
*(Wired Edge
sensor)
S2 0
SENSOR #2 TYPE
Same as Sensor 1 Same as Sensor 1 SENSOR 2
COM
+24V
SENSOR COM
S3 0
SENSOR #3 TYPE
Same as Sensor 1 Same as Sensor 1 SENSOR 3
COM
+24V
SENSOR COM