110 IBM NeXtScale System Planning and Implementation Guide
4.17 Physical specifications
The IBM NeXtScale nx360 M4 features the following physical specifications:
򐂰 Dimensions:
Height: 41 mm (1.6 in)
Depth: 658.8 mm (25.9 in)
Width: 216 mm (8.5 in)
Weight estimation (based on the LFF HDD within computer node): 6.05 kg
(13.31 lb)
򐂰 Environment
The NeXtScale nx360 M4 compute node complies with ASHRAE class A3
specifications.
򐂰 Power on (chassis is powered on):
Temperature: 5°C - 40°C (41°F - 104°F)
1
Humidity, non-condensing: -12°C dew point (10.4°F) and 8% - 85%
relative humidity
2
,
3
Maximum dew point: 24°C (75°F)
Maximum altitude: 3048 m (10,000 ft)
Maximum rate of temperature change: 5°C per hour (41°F per hour)
4
81Y9944 300GB 15,000 rpm 6Gb SAS 2.5" HDD 24
00W1595 600GB 10,000 rpm 6Gb SAS 2.5" HDD 24
46W0970 900GB 10,000 rpm 6Gb SAS 2.5" HDD 24
46W0980 1.2TB 10,000 rpm 6Gb SAS 2.5" HDD 24
2.5" SAS HS SSDs
49Y6072 200GB 6Gb SAS 2.5" SSD 24
49Y6077 400GB 6Gb SAS 2.5" SSD 24
Part
number
Description Maximum supported
per one enclosure
1
A3 - Derate maximum allowable temperature 1°C/175 m above 950 m
2
The minimum humidity level for class A3 is the higher (more moisture) of the -12°C dew point and
the 8% relative humidity. These intersect at approximately 25°C. Below this intersection (~25°C),
the dew point (-12°C) represents the minimum moisture level; above the intersection, relative
humidity (8%) is the minimum.