Table 25. 101-711 through FFC-725 SRNs (continued)
SRN FFC Description and Action
651-786 304 214 Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-789 2CD 214 Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-78A 2CE 214 Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-78B 2CC 214 Uncorrectable memory error. Go to “Performing the checkout procedure” on page
184.
651-809 Power fault warning due to unspecified cause.
Go to “Performing the checkout procedure” on page 184.
651-810 2E2 Over-voltage condition was detected.
Do the following procedure before replacing any FRUs:
1. Shut the system down.
2. Visually inspect the power cables and reseat the connectors.
3. Run the following command diag -Avd sysplanar0. When the Resource Repair
Action menu displays, select sysplanar0.
651-811 2E2 Under voltage condition was detected
Do the following procedure before replacing any FRUs:
1. Shut the system down.
2. Visually inspect the power cables and reseat the connectors.
3. Run the following command diag -Avd sysplanar0. When the Resource Repair
Action menu displays, select sysplanar0.
651-813 System shutdown due to loss of ac power to the site. System resumed normal
operation, no action required.
651-818 Power fault due to manual activation of power-off request. Resume normal
operation.
651-820 2E1 An over-temperature condition was detected.
1. Make sure that:
v The room ambient temperature is within the system operating environment
v There is unrestricted air flow around the system
2. Replace the system-board.
651-821 2E1 System shutdown due to an over maximum temperature condition being reached.
1. Make sure that:
v The room ambient temperature is within the system operating environment
v There is unrestricted air flow around the system
2. Replace the system-board.
651-822 2E1 System shutdown due to over temperature condition and fan failure. Use the
physical FRU location(s) as the probable cause(s). Use the physical location codes to
replace the FRUs that are identified on the diagnostics problem report screen.
651-831 2E2 Sensor detected a voltage outside of the normal range. Go to “Performing the
checkout procedure” on page 184.
651-832 G2E1 Sensor detected an abnormally high internal temperature. Make sure that:
1. The room ambient temperature is within the system operating environment.
2. There is unrestricted air flow around the system.
3. There are no fan failures.
Chapter 2. Diagnostics 135