SERVICING
Ideal Logic Code Combi - Installation and Servicing
42
SERVICING SCHEDULE
F

WARNING. Always turn OFF the gas supply at the gas service cock, and switch OFF and disconnect the electricity
supply to the appliance before servicing.
Combustion testing must be carried out by a competent person using a combustion analyser conforming to BS7927.





INSPECTION
1. 

2.

3.
any suspect joints ensuring a gas tightness check is carried


CLEANING PROCEDURE
Note. In order to carry out either servicing or replacement of


1. 
2. 

3. 

4. 


5. 

and 
IMPORTANT.
6. After completing the servicing or exchange of components

7. 

Do NOT OPERATE the boiler if the front panel is

8. If, for any reason, the condensate trap/siphon has been


9. 
10. 

CO & CO
2
If the CO/CO
2




11. Complete the service section in the Benchmark

GENERAL
Please Note: During routine servicing, and after any
maintenance or change of part of the combustion
circuit, the following must be checked:
 
 
the relevant seals
 

 
 
COMPETENCE TO CARRY OUT THE CHECK
OF COMBUSTION PERFORMANCE
Please Note 

rated input not exceeding 70kW net advises that:
 
measurement should have been assessed as


 

and be calibrated in accordance with the analyser
manufacturers requirements, and
- Competence can be demonstrated by satisfactory

covers the use of electronic portable combustion


Flue Sampling
Point
206279-10270
SERVICING
206279-1.indd 36 06/01/2011 09:10:25