FAULT FINDING
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
Ideal Logic Code Combi - Installation and Servicing
79
ALTERNATING ‘L AND ‘1’ - FLOW TEMPERATURE OVERHEAT LOCKOUT

isolation and radiator valves open?

Fill and vent the system and open all
isolation valves, then reset boiler
Is the Flow/Return Differential across the Boiler in
excess of 30°C?
NO

the Differential now below 20°C?

NO

to Frame 53)

then reset boiler
NO
OK, now
reset boiler

80
ALTERNATING ‘L AND ‘2’ - IGNITION LOCKOUT
If the boiler is reset does the boiler
ignite for a short time and then
extinguish?



Check the detection electrode
and associated harness for:
continuity, visual condition and

Check if the condensate pipe is


Replace as necessary
NO
Check gas supply and
rectify fault
NO

Is 215Vdc supply available at the



Check spark generator and
associated harness for: continuity


correctly?

Check ignition electrode and
associated harness for: continuity,

(Refer to Frame 54) Are these
functioning correctly?
NO
Check siphon and condensate
drain pipe work for blockage and

working OK?
Check wiring connection



NO

Generator and harness
as necessary
NO
Replace Ignition
Electrode and
associated harness as
necessary
NO
Replace Gas Valve

* Note: due to the wave form of the rectied voltage, the reading will vary depending on the type of meter used to measure the
value. In general terms a reading greater than 150V indicates that the correct voltage is supplied to the gas valve.

between outside pins 4k (± 2)?

Replace Gas Valve
NO
RESET PROCEDURE
RESET PROCEDURE