1.11 ELECTRICAL SUPPLY
Wiring external to the appliance MUST be in accordance with
the current I.E.T. (BS7671) Wiring Regulations and any local
regulations which apply. For Ireland reference should be made to
the current ETCI rules for electrical installations
The point of connection to the mains should be readily accessible
and adjacent to the boiler.
1.12 CONDENSATE DRAIN
Refer to 19
A condensate drain is provided on the boiler. This drain must be
connected to a drainage point on site. All pipework and ttings in
the condensate drainage system MUST be made of plastic - no
other materials may be used.
IMPORTANT.
Installation must be in accordance with BS 6798.
The drain outlet on the boiler is sized for standard 21.5mm
overow pipe. It is a universal tting to allow use of different
brands of pipework.