2.13 OPEN FLUE KITS
Contents
221216 / 221218
• Air inlet grille
158771 / 158772
• Extension tube (x2)*
158769 / 158770
• Terminal
Note: See Section 2.15 for elbow equivalent lengths.
2.11 VERTICAL ROOF FLUE KIT
Contents
• Terminal
• Locking Collar
• Finishing plates (x2)
• Bracket
Note: See Section 2.15 for elbow equivalent lengths.
2.12 VERTICAL ROOF FLUE KIT
Contents
• Increaser
• Terminal
• Locking Collars (x2)
• Finishing plates (x2)
• Bracket
Note: See Section 2.15 for elbow equivalent lengths.
Vertical concentric ue application ~ maximum lengths
Model 30/30P 40/40P 60/60P 80/80P 100/100P 120/120P 150
Max ue length (m) 33 30 17.5 10 10 9 6
Flue Size 80 / 125 100 / 150
Vertical ue kit No 220915 220918
60 & 80 vertical concentric ues of longer length
Model 60/60P 80/80P
Max ue length (m) 28 18
Flue Size 100 / 150
Vertical ue kit No 220916
Open ue application ~ maximum lengths and pressure differentials
Model 30/30P 40/40P 60/60P 80/80P 100/100P 120/120P 150
Max ue length (m) 65 70 25 15.3 20 49 32
Max ue press diff (Pa) 180 277 146 312 220 473 332
Flue Size 80/125 100/150
Open ue kit No 221216 + 158771 + 158769 221218 + 158772 + 158770