2.8 FLUE SYSTEMS
2.9 HORIZONTAL WALL FLUE KIT
2.10 HORIZONTAL WALL FLUE KIT - For longer ue lengths for the 60 & 80kW
A comprehensive range of ue kits are available from
Ideal Boilers. Examples of horizontal and vertical concentric
and open ue options are demonstrated on the following pages.
Tables are provided with these examples, giving the maximum
extensions which may be added.
For horizontal ues: this is the distance from the ue outlet
centre line on the boiler to the outside wall.
For vertical ue: this is the distance from the top of the boiler
case to the aperture in the weather collar.
If elbows are to be used, then the equivalent length of that
tting (see page 21) must be subtracted from the maximum ue
extensions allowed for that ue option.
Note: Horizontal terminal resistance includes 1 x 90
o
elbow.
A multiple boiler ue header system is available ‘Ideal Multiline’.
This permits up to 6 boilers to be connected to a single ue
header with a maximum total output of 600kW.
Other ue header systems should be designed and supplied
by a specialist ue company. BS 6644 and IGE UP/10 provide
guidance on design and the drainage of condensate from ue
stack and headers. Condensate from a ue stack and header
must be collected and drained before entering the boiler.
For room sealed ues concentric ues must be used.
NOTE. When installing an Evomax 2 boiler onto an exisitng
Muliline system, you must remove the non-return valve
assembly and replace with either of the following Multline
Extensions (exluding NRV):
80 dia = Part No. 220968
100 dia = Part No. 222068
Note: See Section 2.15 for elbow equivalent lengths.
Note: See Section 2.15 for elbow equivalent lengths.
Horizontal concentric ue application ~ maximum lengths
Model 30/30P 40/40P 60/60P 80/80P 100/100P 120/120P 150
Max ue length (m) 33 30 17.5 10 10 9 6
Flue Size 80 / 125 100 / 150
Wall ue kit No 220920 220921
60 & 80 horizontal concentric ues of longer length
Model 60/60P 80/80P
Max ue length (m) 28 18
Flue Size 100 / 150
Wall ue kit No 220920
18
Installation & Servicing
SECTION 2 - INSTALLATION
INSTALLATION