Note.
Natural gas consumption is calculated using a caloric value of
37.8MJ/m
3
(1038Btu/ft
3
) gross or 34 MJ/m
3
(910 Btu/ft
3
) nett at
15
o
C and 1013.25 mbar.
a. For l/s divide the gross heat input (kW) by the gross C.V. of the
gas (MJ/m
3
)
b. For ft/h
3
divide the gross heat input (Btu/h) by the gross C.V. of
the gas (Btu/ft
3
).
c. For m
3
/h multiply l/s by 3.6.
d. 1kW = 3412 BTU/hr.
e. 1m
3
= 35.3ft
3
f. 1mg/kWh (NOx) = 0.568 ppm DAF (natural gas).
Propane gas consumption is calculated using a caloric value of
95.7 MJ/m
3
(2500 Btu/ft.
3
) gross or 88.0 MJ/m
3
(2300 Btu/ft.
3
) net
at 15
o
C and 1013.25 mbar.
To obtain the fuel consumption in liquid form divide the above
gures by 270.
** The value is used in the UK Government’s Standard Assessment Procedure (SAP) for energy ratings of dwellings. The test data from which it has been calculated have
been certied by a notied body.
Table 2 General Data
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989. The manufacturer’s
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT. These appliances are CE certied for safety
and performance. It is, therefore, important that no external
control devices, e.g. ue dampers, economisers etc., are
directly connected to these appliances unless covered by
these Installation and Servicing Instructions or as otherwise
recommended by Ideal Boilers in writing. If in doubt please
enquire.
Any direct connection of a control device not approved by Ideal
Boilers could invalidate the certication and the normal appliance
warranty. It could also infringe the Gas Safety Regulations and
the above regulations.
Model 30 30P 40 40P 60 60P 80 80P 100 100P 120 120P 150
Boiler Output
(non-condensing)
Mean 70°C
Max kW 30 30 40 40 60 60 80 80 100 100 120 120 150
Min kW 6 6 8 8 12 12 16 16 20 20 24 24 30
Boiler Output
(condensing)
Mean 40°C
Max kW 31.5 30.9 42 41.2 63.5 62.1 84.4 82.6 103.9 101.7 124.7 123.3 158
Min kW 6.5 6.4 8.5 8.3 12.7 12.4 17.2 16.8 21.6 21.3 26 25.7 32.5
Boiler Input
Max Rate
Nett kW 30.4 30.4 40.5 40.5 60.8 60.7 82 81.9 102.4 102.4 122.9 122.9 153.7
Gross kW 33.7 33 44.9 44 67.4 66 90.9 88.9 113.6 111.2 136.4 133.4 170.5
Boiler Input
Min Rate
Nett kW 6.1 6.1 8.1 8.1 12.2 12 16.4 16.2 20.5 20.4 24.6 24.5 30.7
Gross kW 6.7 6.6 9 8.8 13.5 13.1 18.2 17.5 22.7 22.2 27.3 26.7 34.1
Gas Rate Max Rate m
3
/hr 3.2 1.26 4.3 1.69 6.4 2.53 8.7 3.41 10.8 4.35 13 5.23 16.2
Flue Gas Flow Rate
Max Rate m
3
/hr 41.3 44.09 54.05 61.68 80.65 88.66 110.1 121.57 140.5 153.6 173.33 183.81 210.7
CO
2
(±0.5%) *
Max Rate % 9.76 10.9 10.2 11.2 9.4 11.4 9.3 11.4 9.4 10.8 9.62 11.2 9.44
Min Rate % 8.56 10.3 8.6 9.7 8.6 10.2 8.7 10.8 8.6 10.1 8.98 10.1 8.51
DB 55.2 55.2 57.7 57.7 59 59 59.9 59.9 62 62 62 62 59
NO
x
(gross) weighted mg/kWh 34.1 52.3 33.2 64.4 35.2 67.7 34.9 63.2 34.8 65.3 33.9 41.6 35.7
Efciency
Seasonal % 96.7 97.2 96.2 96.7 96.4 96.9 97.2 97.7 96.7 96.7 96.6 96.6 96.7
**SEDBUK 2009 % 89.6 90.6 89.3 90.3 89.4 90.5 n/a n/a n/a n/a n/a n/a n/a
Max. operating temp sealed sys.
ºC 85
Max. operating temp open vented
sys. ºC 82
*CO
2
measurements taken using controlled reference natural gas. Readings on mains gas quality may vary
Model 30 30P 40 40P 60 60P 80 80P 100 100P 120 120P 150
Gas Supply 2H – G20 – 20mbar / 3P - G31 - 37mbar
Gas Supply Connection G ¾
Flow Connection G 1¼
Return Connection G1¼
Max Pressure (sealed sys)
Bar (psi)
6.0 (87)
Maximum Static Head
m
61.0
Electricity Supply 230V - 50Hz
Fuse Rating
A
4.0
Power Consumption
W
81 138 82 149 187 243 240
IP Rating IPX4D
Nominal ue dia - Concent. 80/125 100/150
Condensate Drain
mm
25
Water Content
L
3.0 5.0 7.0 9.2
Packaged
Kg
53.5 63.5 80 88
Unpackaged (dry weight)
Kg
47.5 57.5 73 81
Table 1 Performance Data (Natural Gas & Propane (P))