EasyManua.ls Logo

IDEAL Logic Code Combi ES26

IDEAL Logic Code Combi ES26
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
INsTaLLaTION
Ideal Logic Code Combi ES - Installation and Servicing
22
CONDENsa TE DRaIN
203
47
149
Condensate
Drain



All condensate pipework should conform to the following:
 


 
 
22mm OD)
 

 

 

 


 
into the dwelling in the event of a blockage (through freezing)
 

In order to minimise the risk of freezing during prolonged very cold
spells, one of the following methods of terminating condensate

Internal Drain Connections
Wherever possible, the condensate drainage pipe should be routed
to drain by gravity to a suitable internal foul water discharge point
such as an internal soil and vent stack or kitchen or bathroom

Condensate pump
Where gravity discharge to an internal termination is not physically
possible or where very long internal pipe runs would be required
to reach a suitable discharge point, a condensate pump of a

should be used terminating into a suitable internal foul water
discharge point such as an internal soil and vent stack or internal

External Drain Connections

only be considered after exhausting all internal termination options


If an external system is chosen then the following measures must
be adopted:



 

- When a rainwater downpipe is used, an air break must be
installed between the condensate drainage pipe and the


- Where the condensate drain pipe terminates over an open
foul drain or gully, the pipe should terminate below the grating



- Where the condensate drain pipe terminates in a purpose

condensate drain pipe sections should be run and insulated as

Unheated Internal areas


Ensure the customer is aware of the effects created by a frozen
condensate and is shown where this information can be found in

Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
Minimum
connection
height up to 3
storeys
Soil & vent stack
≥ 450
75
Boilers without 75mm sealed
condensate trap must be fitted with
a 75mm trap and visible air break
Sink/basin/
bath or
shower
Boiler
with 75mm
sealed
condensate
trap
Min Ø 19mm
Internal pipe
Internal soil & vent stack
Boilers without 75mm sealed
condensate trap must be fitted with
a 75mm trap and visible air break
75
≥ 100
≥ 100
Figure 1

Figure 2


continued . . . . .
INsTaLLa TION

Other manuals for IDEAL Logic Code Combi ES26

Related product manuals