Precautions When Using the Product
Do not use an analog I/O module with hardware version number V200 in combination with the system software for analog I/O
modules version 1.01 or lower. The operation mode of the analog I/O module will be indefinite and analog input values cannot be
acquired correctly.
System software version 1.02 is written to V200 analog I/O modules when they are shipped from the factory. Do not download
system software version 1.00 or 1.01 to these analog I/O modules.
If system software version 1.01 or lower is written to a V200 analog I/O module, download the system software for analog I/O
modules version 1.02 included with WindLDR Ver. 8.6.1 or higher to the analog I/O module again.
System Software Version
Hardware Version Number Version 1.01 or Lower Version 1.02 or Higher
Lower than V200 Yes Yes
V200 or Higher No Yes