11.3 Error indications
Warning message
[SC1] Short circuit in OUT1�
LED8forOUT1flashes(→7Operatinganddisplayelements).
[SC2] Short circuit in OUT2�
LED7forOUT2flashes(→7Operatinganddisplayelements).
[SC] Short circuit in both outputs�
LED7andLED8flash(→7Operatinganddisplayelements).
[OL] Detection zone of volumetric flow or temperature exceeded�
[UL] Below the detection zone of volumetric flow or temperature�
[Err] •Unit faulty / malfunction�
•Measured value outside the detection zone�
[C�Loc] Setting pushbuttons locked, parameter change rejected�
Active IO-Link communication�
[S�Loc] Setting pushbuttons locked, parameter change rejected�
Unlock using parameter setting software�
[SEnS] Sensor signal invalid�
•Measuring pipe not sufficiently filled�
•Medium with too low a conductivity�
[IOE�n] Malfunctioning� The unit is faulty and must be replaced�