For installation in pipes:•
The inside pipe diameter (d) must be at least 100 mm� -
Only install the unit in metal pipes� -
For installation in connection pieces:•
The diameter of the connection piece (d) must be at least 50 mm� -
The height of the connection piece (h) must not exceed 40 mm� -
The maximum level must not ex-•
ceed the limit of the block distance
(BD = 30 mm)� If it is exceeded by
more than 10 mm, malfunctions
can occur�
Remedies: arrange for a spout; in-
stall the unit in a connection piece�
Do not install the unit in the immediate vicinity of a fill opening� If possible, •
install a fill pipe (A) in the tank� Minimum distance between the fill pipe and the
rod=50mm;higherforrodlengths>70cmandincaseofheavysoiling(→
6�1�1)�